Customization: | Available |
---|---|
Product Specifications: | 20,35,50,75,100kVA |
Working Voltage: | 380V(-40%~+20%) ; 380V(-30%~+15%) |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Three-phase Three-wire High Voltage SVG | |||||
Type | Rated voltage (KV) |
Rated current (A) |
Compensation current (A) |
Size(mm) Width*Height*Depth |
remarks |
SVG-6/2.4 | 6 | 1.2±1.2 | 230 | 4500*1200*2400 | In the table is the SVG capacity of chain star connection. The cooling mode is air cooling |
SVG-6/4.8 | 6 | 2.4±2.4 | 460 | 4800*1200*2400 | |
SVG-6/8 | 6 | 4.0±4.0 | 768 | 6000*1200*2400 | |
SVG-6/10 | 6 | 5.0±5.0 | 960 | 7800*1200*2600 | |
SVG-10/2.0 | 10 | 1.0±1.0 | 116 | 6000*1200*2400 | |
SVG-10/4.0 | 10 | 2.0±2.0 | 230 | 6000*1200*2400 | |
SVG-10/8.0 | 10 | 4.0±4.0 | 460 | 7500*1200*2400 | |
SVG-10/10 | 10 | 5.0±5.0 | 576 | 7500*1200*2400 | |
SVG-35/16 | 35 | 8.0±8.0 | 264 | 4600*25000 | area covered |
SVG-35/32 | 35 | 16±16 | 528 | 4600*30000 | |
SVG-35/60 | 35 | 30±30 | 1000 | 5600*36000 | |
SVG-35/80 | 35 | 40±40 | 1336 | 8000*18000 |
Wall mounted | |||||||||
type | width (mm) |
height (mm) |
depth (mm) |
mounting hole (mm) |
|||||
L | L1 | H | H1 | D | D1 | D2 | d | i | |
35kavr | 381 | 375 | 174 | 170 | 623 | 580 | 550 | 600 | 300 |
50kvar | 506 | 500 | 204 | 200 | 623 | 580 | 550 | 600 | 400 |
75kvar | 506 | 500 | 244 | 240 | 653 | 616 | 580 | 630 | 400 |
100kvar | 506 | 500 | 274 | 270 | 710 | 670 | 638 | 685 | 400 |
Rack-mounted | |||||||||
type | width (mm) |
height (mm) |
depth (mm) |
mounting hole (mm) |
|||||
L | L1 | H | D | D1 | d | i | h1 | D2 | |
35kvar | 415 | 375 | 170 | 580 | 550 | 413 | 300 | 35 | 405 |
50kvar | 570 | 500 | 200 | 580 | 500 | 538 | 120 | 38.5 | 535 |
75kvar | 570 | 500 | 240 | 616 | 580 | 538 | 160 | 40 | 535 |
100kvar | 570 | 500 | 270 | 670 | 638 | 538 | 190 | 40 | 535 |
Type | Rated voltage(V) | Rated capacity(KVAR) | MinSize(mm) Width*Height*Depth |
SVG-380/200 | 400 | 100±100 | 800*600*2200 |
SVG-380/300 | 150±150 | 2*(800*600*2200) | |
SVG-380/400 | 200±200 | 2*(800*600*2200) | |
SVG-380/600 | 300±300 | 2*(800*600*2200) | |
SVG-660/200 | 690 | 100±100 | 1000*800*2200 |
SVG-660/400 | 200±200 | 2*(1000*800*2200) | |
SVG-660/600 | 300±300 | 3*(1000*800*2200) | |
SVG-660/800 | 400±400 | 4*(1000*800*2200) | |
SVG-1140/400 | 1140 | 200±200 | 2*(1000*800*2200) |
SVG-1140/800 | 400±400 | 3*(1000*800*2200) | |
SVG-1140/1200 | 600±600 | 4*(1000*800*2200) | |
SVG-1140/1600 | 800±800 | 5*(1000*800*2200) |
Working voltage | 380V(-40%~+20%) ; 380V(-30%~+15%) |
Working frequency | 50/60Hz±5Hz |
Wiring mode | Three-phase three-wire ; Three-phase four-wire |
Current sampling | 5A(CT:100/5~10000/5) |
Current sampling position | Load side / grid side optional |
Circuit topology | Three level |
Number of parallel units | Unlimited |
Switching frequency | 21.6KHz |
Cooling mode | Intelligent air cooling |
Filtering range | 2-13 times(50% of rated current) |
Reactive power compensation | -100%~+100%(Power factor can be set) |
Three phase unbalance | 100% unbalance full compensation |
overload protection | support |
power factor | -1~+1 |
Instantaneous response time | <100us |
Total response time | <10ms |
Noise | <70dB |
Protection function | Over voltage protection, under voltage protection, short circuit protection, inverter bridge reverse protection, etc |
Expand function | The 10 channel TSC interface can operate with TSC / TSF |
Communication interface | RS485 Network port |
Communication protocol | General agreement on electricity;modbus protocol;YCP/IP |
Upper computer software | Yes, all parameters can be set by upper computer |
Display interface | 3 / 7 Inch Touch Screen |
Display information | Voltage, current, power, harmonic and other grid parameters |
Monitor | Support independent monitoring / centralized monitoring of each module |
Fault alarm | Up to 500 alarm messages can be recorded |
USAGE ENVIRONMENT:
Ambient temperature | -20ºC~+45ºC |
Storage temperature | -40ºC~+65ºC |
Relative humidity | Maximum 95% frost free |
Altitude | Below 1500m, the power will be reduced by 1% every 100m |
Protection level | IP20,Higher protection level can be customized |
Installation mode | Wall mount, rack, whole machine |
Incoming line mode | Back feed, upper feed |