• Intelligent Purification Non-Contact Compensating AC Regulator Zsbw-150 Communications Station
  • Intelligent Purification Non-Contact Compensating AC Regulator Zsbw-150 Communications Station
  • Intelligent Purification Non-Contact Compensating AC Regulator Zsbw-150 Communications Station
  • Intelligent Purification Non-Contact Compensating AC Regulator Zsbw-150 Communications Station
  • Intelligent Purification Non-Contact Compensating AC Regulator Zsbw-150 Communications Station
  • Intelligent Purification Non-Contact Compensating AC Regulator Zsbw-150 Communications Station

Intelligent Purification Non-Contact Compensating AC Regulator Zsbw-150 Communications Station

Current Type: AC
Phase: Three Phase
Frequency Characteristics: High Frequency
Usage: SVC, DBW, Zsbw
Frequency: Industrial Frequency
Size: Large
Customization:
Manufacturer/Factory & Trading Company
Gold Member Since 2007

Suppliers with verified business licenses

Shanghai, China
to see all verified strength labels (26)

Basic Info.

Model NO.
Zsbw-30
Iron Core Shape
Ring
Power Source
Linear Regulated Power Supply
Brand
Wenlida
Transport Package
Wooden Case
Trademark
WENLIDA
Origin
China
HS Code
85044019
Production Capacity
20000PCS/M

Product Description

 ZSBW, ZDBW three-phase, single-phase intelligent and purified no-contact compensating alternative stabilizers are new products combining the most advanced technology abroad with our national condition. It uses micro-program process, light and electrical transmission, no-contact switch, compensated alternative stabilizing technology, and has advantages of high efficiency, energy saving, quick adjustment, no noise, no connected spot, anti-interference, auto adjustment  according to each phase, full function, high reliability, long life, free of maintenance. It's also equipped with RS-232 interface and can realize promote control and test.
This series is widely used in the places requiring stable voltage such as communication equipments, broadcast and TV stations, in dustrial production line, digitally controlled machine, textile industry, medical equipments, hotels, computer rooms, etc.
Intelligent Purification Non-Contact Compensating AC Regulator Zsbw-150 Communications Station

Intelligent Purification Non-Contact Compensating AC Regulator Zsbw-150 Communications Station
According to the change of the input voltage of the power grid line, the analog signal of the changed voltage is transformed into digital signal through sampling by the voltage detection unit, which is processed by microcomputer, preprogrammed program and prefabricated data. The intelligent control system sends commands to the optocoupler to drive the non-contact and fast electronic switching circuit to compensate the output voltage appropriately and accurately, so as to adjust the output voltage within the allowable error of accuracy, so as to achieve the purpose of automatic voltage stabilization.
Technical data
input Range Three phase five wire 380V ± 15% (wider range can be customized)
frequency 50/60HZ
transport
Out
Rated voltage Three phase 380V
Voltage stabilizing accuracy ±2%
response speed <10ms
Additional voltage harmonic THD No additional waveform distortion (static)
Efficiency ≥98%
Three phase unbalance Three phase voltage automatic balance
Delay output Stabilize voltage before output (protect equipment from impact)
protect Over voltage When the output phase voltage exceeds 10%, it can be set to cut off the output or uninterrupted transferring to the  bypass or no action,can be set
Under voltage When the output phase voltage is lower than 10%, it can be set to cut off the output or uninterrupted transferring to the  bypass or no action, can be set
Lack of phase automatic cut-off
Phase sequence error Yes, digital phase detection technology is adopted, which is accurate and reliable, and can effectively avoid misoperation caused by harmonic interference
overload Electronic detection, output can be cut off within 3 minutes of overload or uninterrupted transferred to the bypass, can be set
Over current Electronic detection and circuit breaker fulfill dual protection
short circuit Electronic detection and circuit breaker fulfill dual protection
bypass Uninterrupted automatic bypass
Display Voltage A,B,C,ΣABC three phases have true RMS touch screen display respectively
electric current A,B,C,ΣABC three phases have true RMS touch screen display respectively
working condition Voltage stabilizing state / mains state
abnormal Overvoltage, undervoltage, overload, fuse failure, phase loss and phase dislocation
operation mode It has two working modes: voltage stabilization and mains power
Overload capacity 1.2Times the rated current for 30 minutes
interface The intelligent man-machine interface operation panel is convenient for setting and querying various parameters
Performance characteristics
Fast response 12Bit high-speed AD acquisition, 128 wave acquisition points per cycle, digital processing and operation by single chip microcomputer, and rapid compensation by electronic module
Multiple adjustment modes can be set Simultaneous regulation: when simultaneous regulation is set, AD simultaneously collects the true effective values of three-phase voltages a, B and C for average calculation, and gives instructions for compensation, which can effectively improve the imbalance of three-phase voltage
Individual regulation: when individual regulation is set, the three-phase voltages are adjusted respectively to ensure that the three-phase voltages are within the accuracy range, especially suitable for single-phase load
Automatic judgment: microcomputer automatic analysis should carry out simultaneous or individual regulation.
Advanced measurement technology 12Bit AD acquisition, digital filtering and true RMS calculation by single chip microcomputer
Accurate control Perfect cooperation between large-scale programmable logic device and single chip microcomputer
Humanized Interface Various indicators (output voltage, voltage stabilizing accuracy and protection function) can be set through the touch keys on the operation panel
No distortion of output waveform Contactless zero crossing switch switching, same frequency, phase locking and sine wave superposition compensation principle
Resistance to harmonic interference True RMS voltage detection
Wide load range Resistive, capacitive and inductive loads can be adapted
Slow start and impact resistance voltage stabilization first before output
Full protection function In case of overvoltage and undervoltage, it can be protected within 1s or automatically switched to bypass without interruption, and has perfect phase loss, overload, short-circuit protection and sound alarm function after fault
Voltage and current display The true RMS values of voltage and current are displayed on the touch screen
 
Component brand
Device name Manufacturer Device name Manufacturer
Thyristor IR chip domestic packaging air switch Chint
transformer High quality silicon steel sheet is adopted Control chip ARM